H-302C control unit
Datasheet: | Download |
The H-302 control unit is the simplest solution of the CENTRALTEST system that allows to monitor up to 7936 luminaires and operate using a touch screen.
The main purpose of H-302C unit is supervision and control over efficiency of all connected system components.
FEATURES
• Initiation of automatic and manual tests of all system components
• Test results registration
• Generation of alarms in case of any failure
• Saving test results on the external USB memory
• Automatic luminaires control in the group addressing system
• Control of luminaires from fire safety group
• Night lighting control
• Connection to BMS
TECHNICAL DATA
Supply voltage | 230V AC 50Hz |
Power consumption | 5VA |
Protection class | I |
Ingress protection | IP65 |
Radio-electric disturbances | N level |
Line galvanic separation | 1500V |
Line loading (1 of 4) | Max. 64 luminaires or 31 expanders |
Emergency operation time (taw) | 3h |
Number of the serviced luminaires | 7936 – independent addresses |
Group controlling | Max. 4 groups + 1 fire protection group |
Zones controlling | Max. 127 zones |
Tests | A, B, C Test |
Communication line length | Max. 1000m |
MATERIAL
Housing material – high quality ABS plastic and polycarbonate
Housing Colour – RAL 7035 / RAL 7024
APPLICATION
The CENTRALTEST system installation consists of combined CT luminaires in parallel to the control unit with the EIA/TIA-485 line. Maximum 64 luminaires may be placed on one control unit line. To connect a larger one number of devices should be used H-311 CTB-CTB network expander. The network expander output creates separate lines for subsequent 64 devices.