Description:
SPARK SGN LED is a low power surface mounted LED luminaire designed for emergency escape lighting. Its main task is to indicate escape routes by means of internally illuminated evacuation sign in the ISO 7010 standard.SPARK SGN LED is compatible with all emergency lighting systems offered by HYBRYD.
FEATURES:
• Luminaire shows the directions of escape• LED indicators signalling the luminaire state
• Deep discharge battery protection
• Maintained/non-maintained operation mode
• Possibility of connecting to the monitoring system or collective power supply system
• Wall mounting
• Housing is made of aluminum, lamp shade of PC
• Installation inside the building
• Two size variants
AVAILABLE SYSTEMS:
ST, AT, CT, CB, CBAM, LVAMMATERIAL:
Housing material – powder coated aluminumHousing colours – RAL 9003, RAL 9006, RAL 9005, other on special order
Lamp shade material – PC
Technical data:
Supply voltage | ST, AT, CT | 230V AC 50/60Hz |
---|---|---|
CB | 230V AC 50/60Hz80–275V DC | |
CBAM | 230V AC 50/60Hz170–275V DC | |
LVAM | 15–32V DC | |
Protection class | ST, AT, CT, CB, CBAM | I |
LVAM | III | |
Ingress protection | IP40 | |
Light source | LED Strips 1) | |
Light colour temperature | 5000K | |
Colour rendering index | 70 | |
Light source supply power | 2W | |
Light source lifespan | > 50 000h | |
Battery type | ST, AT, CT | Ni-MH |
Battery charging time | ST, AT, CT | < 24h |
Emergency operation time | ST, AT, CT | 1h, 3h |
Ambient temperature | ST, AT, CT | +5 – +45˚C |
CB, CBAM | -10 – +55˚C | |
LVAM | -25 – +60˚C | |
Suitable for through wiring | YES |