- SUNON RND
SUNON RND
Files:
Datasheet: | Download |
Photometric data: | Download |
Description:
SUNON RND and SUNON SQR are surface-mounted luminaires with medium LED power and high efficiency, designed for emergency lighting. Its main task is to illuminate escape routes, evacuation signs, rooms in public facilities, work places, etc.FEATURES:
• Deep discharge battery protection• Non-maintained, switched maintained or night operation mode
• Night operation and fire mode available for CENTRALTEST system
• Possibility to connect to the central management system, central power supply or group power supply
• Lighting of escape routes, open spaces and fire points
• Small housing made of plastic
• Many variants of luminaire power
• Wiele wariantów mocowania
• Wide range of optics
AVAILABLE SYSTEMS:
STANDARD – manual testsAUTOTEST – internal components, battery and light source tests being performed automatically
CENTRALTEST – internal components, battery and light source tests being performed on command from the main unit of central management system
CTRF – centraltest only with the RF communication module
CTBT – centraltest only with the BT communication module
CTW – centraltest with BT + RF radio communication
CB – luminaire supplied from HVCBS (230V AC / 216V DC / 108V DC), without address module
CBAM – luminaire supplied from the HVCBS (230V AC / 216V DC), with built-in address module
LVAM – luminaire supplied with 24V DC from the LVDBS system, with built-in address module
MATERIAL:
Housing material – PC/ABS mixHousing colour – RAL 9016, RAL 7042, RAL 7016, RAL 9005
Technical data:
Supply voltage | ST, AT, CT | 230V AC 50/60Hz | |
---|---|---|---|
CB, CBAM | 230V AC 50/60Hz170–275V DC | ||
LVAM | 10–32V DC | ||
Protection class | ST, AT, CT, CB, CBAM | II | |
LVAM | III | ||
Ingress protection | IP54 | ||
Light source | LED module 1) | ||
Light colour temperature | 5700K | ||
Colour rendering index | 70 | ||
Light source supply power | 1W, 2W, 3W, 5W | ||
Light source lifespan | > 50 000h | ||
Battery type, voltage | Li-Ion, 7.4V | ||
Battery capacity | 0.7, 2.2, 4.4Ah | ||
Battery recharging time | < 12h | ||
Emergency operation time | 1h, 3h, 8h | ||
Ambient temperature | ST, AT, CT | +5 – +35˚C;TE: 2) -25 – +35˚C | |
CB, CBAM | -10 – +40˚C; | ||
LVAM | -25 – +45˚C | ||
Supply cable cross-section area | 0.5 – 2.5mm2 | ||
Supply cable diameter | ≤ 16mm | ||
Communication cable diameter | CT | ≤ 7mm | |
Through wiring | YES | ||
Suitable for surface wiring | NO |
2) TE – extended temperature range