- PROFILIGHT SGN
PROFILIGHT SGN
Files:
Datasheet: | Download |
Manual: | Download (ST AT CT) Download (CB CBAM LV LVAM) |
CNBOP: | Download |
Hygienic certificate: | Download |
Description:
PROFILIGHT SGN LED is a low power LED luminaire designed for emergency escape lighting installed inside buildings. Depending on the mounting type allows for the surface, suspended or recessed installation. Its main task is to indicate escape routes by means of internally illuminated evacuation signs in the ISO 7010 standard.The luminaire consists of two parts. The main part with electronics, battery, LED strip and lamp shade for evacuation sign is invariable of mounting method. The mounting part is variable and is dedicated to various types of mounting. It is possible to order luminaire without a lamp shade with evacuation sign. PROFILIGHT SGN LED is compatible with all emergency lighting systems offered by HYBRYD.
FEATURES:
• Luminaire shows the directions of escape• LED indicators signalling the luminaire state
• Deep discharge battery protection
• Maintained/non-maintained operation mode
• A lot of mounting types
• Housing is made of aluminum, lamp shade of PMMA
• Installation inside the building
AVAILABLE SYSTEMS:
ST, AT, CT, CB, CBAM, LVAMMATERIAL:
Housing material – powder coated aluminumHousing colours – RAL 9003, other on special order
Lamp shade material – PMMA
Technical data:
Supply voltage | ST, AT, CT | 230V AC 50/60Hz |
---|---|---|
CB | 230V AC 50/60Hz 80–275V DC | |
CBAM | 230V AC 50/60Hz 170–275V DC | |
LVAM | 15–32V DC | |
Protection class | ST, AT, CT, CB, CBAM | I |
LVAM | III | |
Ingress protection | IP40 | |
Light source | LED strip 1) | |
Light colour temperature | 5000K | |
Light source supply power | 1W | |
Light source lifespan | > 50 000h | |
Battery voltage | 4,8V | |
Battery type / capacity | Ni-Cd | 1,0Ah |
Ni-MH | 1,6Ah | |
Battery charging time | < 24h | |
Emergency operation time | ST, AT, CT | 1h, 3h |
Ambient temperature | ST, AT, CT | +5 – +40˚C; TE:2) -20 – +40˚C |
CB, CBAM | -10 – +55˚C; TE:2) -25 – +65˚C | |
LVAM | -25 – +70˚C | |
Supply cable cross-section area | 0,5 – 2,5mm2 | |
Supply cable diameter | ≤ 13mm | |
Communication cable diameter | ≤ 7mm | |
Suitable for through wiring | YES | |
Suitable for surface wiring | YES |
2) TE – extended temperature range
Pictograms:
PI05
PI06
PI15
PI17
PI18
PI21
PI22
PI23
PI24
PI25
PI26
PI27