- PRIMOS II
PRIMOS II
Files:
Datasheet: | Download |
Manual: | Download (ST AT CT) Download (CB CBAM LV LVAM) |
CNBOP: | Download |
Photometric data: | Download |
Hygienic certificate: | Download |
Description:
PRIMOS II is a high power and high efficiency surface mounted LED luminaire, designed for emergency lighting. Its main task is to illuminate escape routes, evacuation signs, rooms in public facilities, work places, etc.A high luminous flux makes it possible to use PRIMOS II up to a height of 14 metres.
PRIMOS II luminaire is compatible with all emergency lighting systems offered by HYBRYD.
FEATURES:
• Deep discharge battery protection• Non-maintained, switched maintained or night operation mode
• Possibility of connecting to the monitoring system or collective power supply system
• Lighting of escape routes, open spaces and fire points
• Adapted to high altitudes
• Housing is made of plastic
• Two light source supply power (5W/7W)
• Wide range of optics
• Possibility to mounting outside the building with additional mounting types C114, W221 or W22
AVAILABLE SYSTEMS:
ST, AT, CT, CB, CBAM, LVAMMATERIAL:
Housing material – PC/ABS mixHousing colours – RAL 9016, RAL 9005, other on special order
Lamp shade material – PC
Technical data:
Supply voltage | AT, CT | 230V AC 50/60Hz |
---|---|---|
CB | 230V AC 50/60Hz 80–275V DC | |
CBAM | 230V AC 50/60Hz 170–275V DC | |
LVAM | 10–32V DC | |
Protection class | ST, AT, CT, CB, CBAM | II |
LVAM | III | |
Ingress protection | IP65 | |
Light source | LED Modules 1) | |
Light colour temperature | 5700K | |
Light source supply power | 5W, 7W | |
Minimum luminous flux (5W/7W) | RO | 553/647 lm |
RP | 547/640 lm | |
RPHV | 553/647 lm | |
AR | 535/626 lm | |
AP | 553/647 lm | |
Light source lifespan | > 50 000h | |
Battery type / napięcie | Ni-Cd | 4,8V |
Ni-MH | 8,4V | |
Battery capacity | 1,0; 1,5; 1,6; 2,1; 2,5; 4,0Ah | |
Battery charging time | < 24h | |
Emergency operation time | 1h, 3h | |
Ambient temperature (5W/7W) | ST, AT, CT | +5 – +35˚C;TE:2) -20 – +35˚C |
CB, CBAM, LVAM | -10 – +45˚C;TE:2) -25 – +50˚C | |
Supply cable cross-section area | 0,5 – 2,5mm2 | |
Supply cable diameter | ≤ 13mm | |
Communication cable diameter | ≤ 7mm | |
Suitable for through wiring | YES | |
Suitable for surface wiring | YES |
2) TE – extended temperature range