- CRYSTAL II 2000
CRYSTAL II 2000
Files:
Datasheet: | Download |
CNBOP: | Download |
Description:
CRYSTAL LED is a high efficiency surface mounted LED luminaire designed for emergency lighting installed inside buildings. Its main task is to illuminate escape routes, evacuation signs, rooms in public facilities, work places, etc.CRYSTAL II is compatible with all emergency lighting systems offered by HYBRYD.
FEATURES:
• Deep discharge battery protection• Non-maintained operation mode
• Possibility of connecting to the monitoring
system or collective power supply system
• Lighting of escape routes, open spaces and fire points
• Housing is made of steel
• Two light source supply power (4W/6W)
• Wide range of optics
• A lot of mounting types
AVAILABLE SYSTEMS:
STANDARD – tests commissioned manuallyAUTOTEST – internal components, battery and light source tests being performed automatically
CENTRALTEST – internal components, battery and light source tests being performed on command from the main unit of central management system
CB – luminaire supplied from HVCBS (230V AC/ 216V DC /108V DC), without address module
CBAM – luminaire supplied from the HVCBS (230V AC / 216V DC), with built-in address module
LVAM – luminaire supplied with 24V DC from the LVDBS system, with built-in address module
MATERIAL:
Housing material – steelHousing colour – RAL 9003, other colours on special order
Technical data:
Supply voltage | ST, AT, CT | 230V AC 50/60Hz |
---|---|---|
CB | 230V AC 50/60Hz80–275V DC | |
CBAM | 230V AC 50/60Hz170–275V DC | |
LVAM | 10–32V DC | |
Protection class | ST, AT, CT, CB, CBAM | I |
LVAM | III | |
Ingress protection | IP40 | |
Light source | LED modules1) | |
Light colour temperature | 5200–5700K | |
Light source supply power | 4W, 6W | |
Minimum luminous flux (2W/4W/6W) | AR | 417 / 642 lm |
AP | 331 / 508 lm | |
RO | 368 / 563 lm | |
RP | 351 / 537 lm | |
Light source lifespan | > 50 000h | |
Battery type / voltage | Ni-MH / 4,8V | |
Battery capacity | 1.6; 2.1; 4.0Ah | |
Battery charging time | < 24h | |
Emergency operation time | 1h, 3h | |
Ambient temperature | ST, AT, CT | +5 – +35˚C |
CB, CBAM | -10 – +45˚C | |
LVAM | -25 – +65˚C | |
Supply cable cross-section area | 0,5 – 2,5mm2 | |
Supply cable diameter | ≤ 13mm | |
Communication cable diameter | CT | ≤ 7mm |
Suitable for through wiring | YES |