- CRYSTAL II
CRYSTAL II
Files:
Datasheet: | Download |
Manual: | Download (ST AT CT) Download (CB CBAM LV LVAM) |
CNBOP: | Download |
Photometric data: | Download |
Description:
CRYSTAL II is a low power LED luminaire designed for emergency escape lighting installed inside buildings. Depending on the mounting type allows for the surface, suspended or recessed installation. Its main task is to illuminate escape routes, evacuation signs, rooms in public facilities, work places, etc.CRYSTAL II luminaire is compatible with all emergency lighting systems offered by HYBRYD.
FEATURES:
• Deep discharge battery protection• Li-Ion battery type
• Adapted to high altitudes
• Maintained/non-maintained or switched maintained operation mode
• Possibility of connecting to the monitoring system or collective power supply system
• Lighting of escape routes, open spaces and fire points
• A lot of mounting types
• Housing is made of steel
• Many luminaire power variants (2-7W)
AVAILABLE SYSTEMS:
AUTOTEST – (AT) internal components, battery and light source tests being performed automaticallyCENTRALTEST – (CT) internal components, battery and light source tests being performed on command from the main unit of central management system
CB – luminaire supplied from HVCBS (230V AC / 216V DC / 108V DC), without address module
CBAM – luminaire supplied from the HVCBS (230V AC / 216V DC), with built-in address module
LVAM – luminaire supplied with 24V DC from the LVDBS system, with built-in address module
MATERIAL:
Housing material – powder coated steelHousing colour – RAL 9003, other colours on special order
Technical data:
Supply voltage | AT, CT | 230V AC 50/60Hz |
---|---|---|
CB | 230V AC 50/60Hz80–275V DC | |
CBAM | 230V AC 50/60Hz170–275V DC | |
LVAM | 10–32V DC | |
Protection class | AT, CT, CB, CBAM | I |
LVAM | III | |
Ingress protection | IP40 | |
Light source | LED modules1) | |
Light colour temperature | CW | 5200 – 5700K |
Light source supply power | 2–7W | |
Light source lifespan | > 50 000h | |
Battery voltage | Li-Ion | 7.4V |
Battery capacity | Li-Ion | 0.7Ah, 2.2Ah, 4.4Ah |
Battery recharging time | AT, CT | ≤ 12h |
Emergency operation time | AT, CT | 1h, 3h, 8h |
Ambient temperature | AT, CT | +5 – +40˚CTE:2) -20 – +40˚C |
CB, CBAM | -10 – +45˚CTE:2) -20 – +45˚C | |
LVAM | -25 – +60˚C | |
Supply cable cross-section area | 0.5 – 2.5mm² | |
Supply cable diameter | ≤ 17mm | |
Communication cable diameter | CT | ≤ 7mm |
Through wiring | ✓ | |
Suitable for surface wiring | ✓ |
2) TE – extended temperature range