Legend
Available systems:
AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
Tests
Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)
Test B - annually executed emergency supply test (emergency work time measurement test)
Work modes:
Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Other functions
Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Mounting
W - mounted to wall
C - mounted to ceiling
C - mounted to ceiling
Other abbreviations
DW - two-sided
H-204 CT T5
SYSTEM VERSION:
CENTRALTESTLIGHT SOURCE:
T5-FQ; T5-FHTECHNICAL DATA:
| Power supply: | 230V AC 50Hz |
|---|---|
| Power consumption: | < 4 VA |
| Protection class: | I |
| Radio noise: | Level N |
| Work frequency: | 25... 30kHz |
| Protection degree: | IP20 |
| Lamp power and type: | FH 14W, 21W, 28W, 35W FQ 24W, 39W, 49W, 54W, 80W |
| Lamp filament preheating: | for FQ 49W, 54W and 80W |
| Communication line: | 2-wired cable (shielded) |
| Accumulator type: | NiCd HT |
| Accumulator voltage: | 4,8V or 8,4V |
| Accumulator capacity: | 1,5Ah, 2,5Ah or 4,0Ah |
| Accumulator charging time: | 24h |
| Emergency work time: | 1h, 2h or 3h (for FQ 49W, 54W and 80W only 2h i 1h) |
| Accumulator lifespan: | 4 years (suggested replacement after 4 years) |
| Temperature ta: | +5ºC ÷ +55ºC |
| Temperature tc: | +70ºC |
| Dimensions (LxDxH): | 240 x 38 x 35 mm |
| Weight (without accumulator): | 400g |
VERSIONS:
| Module name | Work mode | Time | Accumulator | Weight | Code |
|---|---|---|---|---|---|
| H-204 CT T5 14/24/39 3J | Maintained | 3h | 4,8V/4,0Ah | 400g | 3879 |
| H-204 CT T5 14/24/39 2J | Maintained | 2h | 4,8V/2,5Ah | 400g | 3886 |
| H-204 CT T5 14/24/39 1J | Maintained | 1h | 4,8V/1,5Ah | 400g | 3893 |
| H-204 CT T5 21 3J | Maintained | 3h | 8,4V/4,0Ah | 400g | 3909 |
| H-204 CT T5 21 2J | Maintained | 2h | 8,4V/2,5Ah | 400g | 3916 |
| H-204 CT T5 21 1J | Maintained | 1h | 8,4V/1,5Ah | 400g | 3923 |
| H-204 CT T5 28 3J | Maintained | 3h | 8,4V/4,0Ah | 400g | 3930 |
| H-204 CT T5 28 2J | Maintained | 2h | 8,4V/2,5Ah | 400g | 3947 |
| H-204 CT T5 28 1J | Maintained | 1h | 8,4V/1,5Ah | 400g | 3954 |
| H-204 CT T5 35 3J | Maintained | 3h | 8,4V/4,0Ah | 400g | 3961 |
| H-204 CT T5 35 2J | Maintained | 2h | 8,4V/2,5Ah | 400g | 3978 |
| H-204 CT T5 35 1J | Maintained | 1h | 8,4V/1,5Ah | 400g | 3985 |
| H-204 CT T5 49/80 2J | Maintained | 2h | 8,4V/4,0Ah | 380g | 8645 |
| H-204 CT T5 49/80 1J | Maintained | 1h | 8,4V/2,5Ah | 380g | 8652 |
ACCUMULATOR:
Nickel-cadmium accumulators are used to supply emergency modules and they are designed to be operative in higher temperatures. Ending socked allows to connect an accumulator with a module. Standard cable length – 200mm.CONNECTORS:
ORDERING:
While ordering, the following shall be given:- module code or name, for example: 8645 or H-204 CT T5 49/80 2J
- modules quantity
- accumulator code (package-voltage-capacity-connector), for example PAS-84-40-H