Legend

Available systems:

AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY

Tests

Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)

Work modes:

Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special

Other functions

Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided

Mounting

W - mounted to wall
C - mounted to ceiling

Other abbreviations

DW - two-sided

TELESTO AUTOTEST


CASING:

Body material: PC (polycarbonate)
Casing colour: White
Shape: Oval
Lamp cover colour: Semi-transparent, opal

TECHNICAL DATA:

Power supply: 230V AC/50Hz
Protection class: I
Radio noise: Level N
Protection degree: IP65
Recharging time: 24h
Emergency work time: 1h, 2h or 3h
Light sources: TC-DD 28W lamp in one-lamp luminaire version
TC-SEL 11W lamp in two-lamps luminaire version
Accumulator type: NiCd HT albo NiMH
Accumulator lifespan: 4 years (suggested replacement after 4 years)
Ambient temperature: 0°C÷50°C
Protection: Luminaire module termination after lamp failure
Emergency efficiency: 35% for 11W
20% for 28W
Connection block: 4x2,5mm2
Blockade: Yes

VERSIONS:

Luminaire nameWork modeTimeAccumulatorWeightCode
TELESTO AT 3CNon-maintained3h8,4V/4Ah NiMH4685
TELESTO AT 2CNon-maintained2h8,4V/2,5Ah4692
TELESTO AT 1CNon-maintained1h8,4V/4,0Ah4708
TELESTO AT 3JMaintained3h4,8V/4Ah8003
TELESTO AT 2JMaintained2h4,8V/2,5Ah8102
TELESTO AT 1JMaintained1h4,8V/1,5Ah8119
TELESTO AT 3MMieszana3h4,8V/4Ah8126
TELESTO AT 2MMieszana2h4,8V/2,5Ah8133
TELESTO AT 1MMieszana1h4,8V/1,5Ah8140

MOUNTING TYPES:

Mounting type C23
C23
Mounting type W14
W14

ORDERING:

While ordering, the following shall be given:
- product code or luminaire name with pictogram code and mounting type, for example: 4685 W14 or TELESTO AT 3C W14
- luminares quantity

CIRCUIT DIAGRAMS:

Circuit diagram TELESTO AUTOTEST

DIMENSIONS:

Casing TELESTO AUTOTEST