- MARINER AT 218 3C AUTOTEST
Legend
Available systems:
AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
Tests
Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)
Test B - annually executed emergency supply test (emergency work time measurement test)
Work modes:
Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Other functions
Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Mounting
W - mounted to wall
C - mounted to ceiling
C - mounted to ceiling
Other abbreviations
DW - two-sided
MARINER AT 218 3C AUTOTEST
CASING:
| Body: | PC(polycarbonate) |
|---|---|
| Casing colour: | grey |
| Lamp cover colour: | transparent |
CHARACTERISTICS:
Suitable for escape routes lighting during emergency work mode.Luminaire is independent and initiate the tests automatically.
High protection degree offers vast possibilities in closed areas, production halls and areas where different weather conditions are possible.
Supervision of 230V power supply and accumulator condition.
2-lamp luminaire.
Deep accumulator discharge protection.
Automatic switching into emergency mode.
Automatic testing (test A and test B).
BLOCKADE function-WB button.
Optical indication-LED
2,5 mm2 connectors wire diameter suitable
Lamp cover can be removed without tools
TECHNICAL DATA:
| Power supply: | 230V AC/50Hz |
|---|---|
| Power consumption: | 4VA max |
| Protection class: | I |
| Radio noise: | Level N |
| Protection degree: | IP65 |
| Recharging time: | 24h |
| Emergency work time: | 3h |
| Light source: | T8 18W G13 |
| Number of lamps: | 2 |
| Accumulator type: | NiCd HT |
| Accumulator voltage: | 4,8 V |
| Accumulator capacity: | 4,0 Ah |
| Recharging time: | 24h |
| Accumulator lifespan: | 4 years |
| Ambient temperature: | +5°C÷55°C |
| Blockade: | Yes |
INDICATION:
Accumulator and module condition are indicated by LED :Green-accumulator condition:
ON : accumulator is connected and charging
OFF: accumulator is disconnedcted or there is an electrical circuit failure
Red-module condition:
-ON- test A failure or lack of lighting in emergency mode
-SHORT FLASHING-test B failure
-FAST FLASHING-module failure
-OFF: lack of failures
There is no LED indication during emergency mode.
VERSIONS:
| Luminaire name | Work mode | Time | Accumulator | Weight | Code |
|---|---|---|---|---|---|
| MARINER AT 218 3C | Non-maintained | h | 2 x 4,8V/4Ah | 9369 |