- HYPERION AUTOTEST
- HYPERION TESTSYSTEM
- HYPERION CENTRAL BATTERY
- HYPERION STANDARD
Legend
Available systems:
AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY
Tests
Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)
Test B - annually executed emergency supply test (emergency work time measurement test)
Work modes:
Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special
Other functions
Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided
Mounting
W - mounted to wall
C - mounted to ceiling
C - mounted to ceiling
Other abbreviations
DW - two-sided
HYPERION AUTOTEST
CASING:
| Body material: | Aluminium |
|---|---|
| Casing colour: | Grey – RAL 9006, other colours available |
| Lamp cover material: | Plexiglas |
| Shape: | Plexiglas with pictogram |
| Lamp cover colour: | Frosted |
TECHNICAL DATA:
| Power supply: | 230V AC/50Hz |
|---|---|
| Power consumption: | <12W for TL8W or <4W for HYPERION AT LED |
| Protection class: | I |
| Radio noise: | Level N |
| Protection degree: | IP40 |
| Recharging time: | 24h |
| Emergency work time: | 1h, 2h or 3h |
| Light source fluorescent lamp: | TL8W- G5 or White LED 1W |
| Accumulator type: | NiMH HT |
| Accumulator lifespan: | 4 years (suggested replacement after 4 years) |
| Ambient temperature: | 0°C÷50°C |
| Connection block: | 3x2,5mm2 or 4x2,5mm2 |
| Blockade: | Yes |
VERSIONS:
| Luminaire name | Work mode | Time | Accumulator | Weight | Code |
|---|---|---|---|---|---|
| HYPERION AT 3J | Maintained | 3h | 3,6V/4,0Ah | 3114 | |
| HYPERION AT 2J | Maintained | 2h | 3,6V/2,5Ah | 3121 | |
| HYPERION AT 1J | Maintained | 1h | 3,6V/1,5Ah | 3138 | |
| HYPERION AT 3C | Non-maintained | 3h | 3,6V/4,0Ah | 3145 | |
| HYPERION AT 2C | Non-maintained | 2h | 3,6V/2,5Ah | 3152 | |
| HYPERION AT 1C | Non-maintained | 1h | 3,6V/1,5Ah | 3169 | |
| HYPERION AT J LED | Maintained | 3h | 4,8V/1,0Ah | 3053 | |
| HYPERION AT C LED | Non-maintained | 3h | 4,8V/1,0Ah | 3084 | |
| HYPERION DW AT 3J | Maintained | 3h | 3,6V/4,0Ah | 0168 | |
| HYPERION DW AT 2J | Maintained | 2h | 3,6V/2,5Ah | 0175 | |
| HYPERION DW AT 1J | Maintained | 1h | 3,6V/1,5Ah | 0182 | |
| HYPERION DW AT 3C | Non-maintained | 3h | 3,6V/4,0Ah | 0199 | |
| HYPERION DW AT 2C | Non-maintained | 2h | 3,6V/2,5Ah | 0205 | |
| HYPERION DW AT 1C | Non-maintained | 1h | 3,6V/1,5Ah | 0212 | |
| HYPERION DW AT J LED | Maintained | 3h | 4,8V/1,0Ah | 0229 | |
| HYPERION DW AT C LED | Non-maintained | 3h | 4,8V/1,0Ah | 0236 | |
| HYPERION D AT 3J | Maintained | 3h | 3,6V/4,0Ah | 4753 | |
| HYPERION D AT 2J | Maintained | 2h | 3,6V/2,5Ah | 4760 | |
| HYPERION D AT 1J | Maintained | 1h | 3,6V/1,5Ah | 4777 | |
| HYPERION D AT 3C | Non-maintained | 3h | 3,6V/4,0Ah | 4999 | |
| HYPERION D AT 2C | Non-maintained | 2h | 3,6V/2,5Ah | 5064 | |
| HYPERION D AT 1C | Non-maintained | 1h | 3,6V/1,5Ah | 5071 | |
| HYPERION D AT J LED | Maintained | 3h | 4,8V/1,0Ah | 5088 | |
| HYPERION D AT C LED | Non-maintained | 3h | 4,8V/1,0Ah | 5095 | |
| HYPERION D DW AT 3J | Maintained | 3h | 3,6V/4,0Ah | 5101 | |
| HYPERION D DW AT 2J | Maintained | 2h | 3,6V/2,5Ah | 5590 | |
| HYPERION D DW AT 1J | Maintained | 1h | 3,6V/1,5Ah | 5620 | |
| HYPERION D DW AT 3C | Non-maintained | 3h | 3,6V/4,0Ah | 5651 | |
| HYPERION D DW AT 2C | Non-maintained | 2h | 3,6V/2,5Ah | 5682 | |
| HYPERION D DW AT 1C | Non-maintained | 1h | 3,6V/1,5Ah | 5699 | |
| HYPERION D DW AT J LED | Maintained | 3h | 4,8V/1,0Ah | 5705 | |
| HYPERION D DW AT C LED | Non-maintained | 3h | 4,8V/1,0Ah | 5712 |
PICTOGRAMS:

P01

P02

P03

P04

P05

P06

P07

P08

P09

P10

P11

P12

P13

P14

P15

P16

P17

P18

P19

P20

P21

P22

P23

P24

P25

P26

P27
MOUNTING TYPES:
ORDERING:
While ordering, the following shall be given:- product code or luminaire name with pictogram code and mounting type, for example: 3114 P19 W5 or HYPERION AT 3J P19 W5
- luminares quantity