Legend

Available systems:

AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY

Tests

Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)

Work modes:

Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special

Other functions

Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided

Mounting

W - mounted to wall
C - mounted to ceiling

Other abbreviations

DW - two-sided

ALU TESTSYSTEM


CASING:

Body material: Aluminium
Casing colour: White – RAL 9003, other colours available
Lamp cover material: Plexiglas
Shape: Plexiglas with pictogram
Lamp cover colour: Frosted

TECHNICAL DATA:

Power supply: 230V AC/50Hz
Power consumption: <12W
Protection class: I
Radio noise: Level N
Protection degree: IP40
Recharging time: 24h
Emergency work time: 1h, 2h or 3h
Light source: TL G5 lamp
Light source power: 8W
Accumulator type: NiCd HT
Accumulator lifespan: 4 years (suggested replacement after 4 years)
Ambient temperature: 0°C÷50°C
Connection block: 3x2,5mm2 or 4x2,5mm2
Blockade: Yes
Sleep mode: Yes
Remote controller steering: Yes

VERSIONS:

Luminaire nameWork modeTimeAccumulatorWeightCode
ALU TS 3JMaintained3h3,6V/4,0Ah3510
ALU TS 2JMaintained2h3,6V/2,5Ah3527
ALU TS 1JMaintained1h3,6V/1,5Ah3534
ALU TS 3CNon-maintained3h3,6V/4,0Ah3541
ALU TS 2CNon-maintained2h3,6V/2,5Ah3558
ALU TS 1CNon-maintained1h3,6V/1,5Ah3565
ALU D TS 3JMaintained3h3,6V/4,0Ah3572
ALU D TS 2JMaintained2h3,6V/2,5Ah3589
ALU D TS 1JMaintained1h3,6V/1,5Ah3596
ALU D TS 3CNon-maintained3h3,6V/4,0Ah3602
ALU D TS 2CNon-maintained2h3,6V/2,5Ah3619
ALU D TS 1CNon-maintained1h3,6V/1,5Ah3626
ALU DW TS 3JMaintained3h3,6V/4,0Ah0335
ALU DW TS 2JMaintained2h3,6V/2,5Ah0342
ALU DW TS 1JMaintained1h3,6V/1,5Ah0359
ALU DW TS 3CNon-maintained3h3,6V/4,0Ah0366
ALU DW TS 2CNon-maintained2h3,6V/2,5Ah0373
ALU DW TS 1CNon-maintained1h3,6V/1,5Ah0380
ALU D DW TS 3JMaintained3h3,6V/4,0Ah0397
ALU D DW TS 2JMaintained2h3,6V/2,5Ah0403
ALU D DW TS 1JMaintained1h3,6V/1,5Ah0410
ALU D DW TS 3CNon-maintained3h3,6V/4,0Ah0427
ALU D DW TS 2CNon-maintained2h3,6V/2,5Ah0434
ALU D DW TS 1CNon-maintained1h3,6V/1,5Ah0441

PICTOGRAMS:

Pictogram P01
P01
Pictogram P02
P02
Pictogram P03
P03
Pictogram P04
P04
Pictogram P05
P05
Pictogram P06
P06
Pictogram P07
P07
Pictogram P08
P08
Pictogram P09
P09
Pictogram P10
P10
Pictogram P11
P11
Pictogram P12
P12
Pictogram P13
P13
Pictogram P14
P14
Pictogram P15
P15
Pictogram P16
P16
Pictogram P17
P17
Pictogram P18
P18
Pictogram P19
P19
Pictogram P20
P20
Pictogram P21
P21
Pictogram P22
P22
Pictogram P23
P23
Pictogram P24
P24
Pictogram P25
P25
Pictogram P26
P26
Pictogram P27
P27

MOUNTING TYPES:

Mounting type C1
C1
Mounting type C2
C2
Mounting type C3(DW)
C3(DW)
Mounting type C4(DW)
C4(DW)
Mounting type W1
W1
Mounting type W2
W2

ORDERING:

While ordering, the following shall be given:
- product code or luminaire name with pictogram code and mounting type, for example: 3510 P19 W1 or ALU TS PLUS 3J P19 W1
- luminares quantity

CIRCUIT DIAGRAMS:

Circuit diagram ALU TESTSYSTEM

DIMENSIONS:

Casing ALU TESTSYSTEM Casing ALU TESTSYSTEM Casing ALU TESTSYSTEM Casing ALU TESTSYSTEM