Legend

Available systems:

AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY

Tests

Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)

Work modes:

Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special

Other functions

Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided

Mounting

W - mounted to wall
C - mounted to ceiling

Other abbreviations

DW - two-sided

H-300 Emergency lighting system



The general concept of H-300 system is based on two elements - emergency luminaires, which operate independently in emergency mode, and testing system compiling all test results. Every emergency luminaire is equipped with microprocessor system and connected to the central unit (H-302 C) through communication bus. Additionally, there is possibility to replace the H-302 C unit with the H-302 IN interface connected to the computer.


Communication between luminaires and the central unit is carried out with the use of additional elements called H-302 R distributors.
The software installed in the central unit offers:
- Automatic and manual testing of all the elements installed in the system
- Test results record
- Generation of alarms in case of any failure
- Test results printout
- Automatic lamp control in group addressing system
- Fire-fighting group lamps control
- Emergency work deactivation with zone addressing
- Night lighting control

The complete system includes: the central unit, distributors and emergency luminaires. Communication between the central unit, distributors and luminaires is carried out through two-wire bus (YTKSY 1x2x1,0 shielded cable). The central unit can work with four output lines (max). Thirty one distributors can be connected to one line and sixty four luminaires can operate within one distributor. In total, the H-300 system is able to monitor 7936 emergency luminaires.
Maximum distances between the central unit and the distributor and the distributor and the most distant luminaire are 1000m.

H-300 system characteristics:
- communication network structure: according to the client’s specification
- different power supply phases available thanks to galvanic insulation of the communication interface
- every element of the system has its unique identification address
- automatic testing of the system elements
- visualization of emergency luminaires arrangement available
- system condition reporting

Hybryd Ltd. has undertaken the mission of development and implementation of emergency lighting system provided with complete
luminaire control and monitoring suitable for any facility.