Legend

Available systems:

AT - AUTOTEST, automatic test execution
TS - TESTSYSTEM, automatic test execution and remote control
ST - STANDARD, manual testing
CT - CENTRALTEST, central monitoring system
CB - CENTRAL BATTERY

Tests

Test A - monthly executed functionality test
Test B - annually executed emergency supply test (emergency work time measurement test)

Work modes:

Basic work - 230V power supply
Emergency work - accumulator power supply
Work modes switching: basic/emergency mode is switched automatically
J - maintained, works in basic and emergency mode
C - non-maintained, works only in emergency mode
MS - mixed, two lamps work in basic mode, one lamp works in emergency mode
N - night, only for Centraltest. Works like in maintained version. Basic work time can be programmed with the use of the central unit
S - special

Other functions

Blockade - emergency work blockade activated or deactivated by terminals positioning
Sleep mode - emergency work blockade for the time of power supply failure. This blockade is released automatically once the power supply is provided

Mounting

W - mounted to wall
C - mounted to ceiling

Other abbreviations

DW - two-sided

H-357


CASING:

Dimensions (LxDxH) | 240 x 38 x 35 [mm]

TECHNICAL DATA:

Power supply: 230 VAC
216 VDC
Radio noise: Level N
Protection degree: IP20
Number of lamps: 1 or 2
Lamp power and type: TLD 18W, TLD 36W, T5 39W
Module protection: Module termination after lamp failure
Ambient temperature: 0°C÷50°C
Dimensions (LxDxH): 240 x 38 x 35 [mm]

ORDERING:

While ordering, the following shall be given:
- module code or name, for example 0809 or H-357 118TLD
- ballasts quantity

CIRCUIT DIAGRAMS:

Circuit diagram H-357 Circuit diagram H-357

DIMENSIONS:

Casing H-357